Select the UPS and batteries for your load
Add your loads (for example 36 kVA, 10 kVA and 15 kVA) and the backup time you need. We total them, size the UPS, list the Uniline UPS from our catalogue that can carry the load, and design the battery bank: voltage, number of batteries and battery size, with the matching batteries from our range. Print the report or send it to us.
- UPS kVA from all your loads
- Battery count, Ah and strings
- UPS and batteries from our catalogue
Loading the calculator…
Want this checked by an engineer?
Send us your result and we’ll review it and prepare a recommendation and quotation.
Chat on WhatsApp insteadMethod & assumptions
- UPS ratingLoad kVA (or kW ÷ power factor) × (1 + growth) ÷ maximum loading. The default keeps the UPS at 80% load or less with 20% growth.
- Battery currentLoad kW ÷ UPS efficiency ÷ battery DC voltage.
- Battery capacityA Peukert correction (exponent 1.25 for VRLA, 1.2 for tubular, 1.05 for lithium) converts the discharge current and time into a 10-hour rated capacity, then divides by an end-of-life factor of 0.8 (batteries are designed to still deliver at 80% of rated capacity) and adds a 10% design margin; for lithium only 90% of rated capacity is counted. Discharge is taken down to the cell end voltage, so no further depth-of-discharge factor is applied. Below 25 °C lead-acid capacity is reduced by about 0.8% per degree.
- Charger and charging timeCharger current is 10% of the bank Ah for lead-acid and 30% for lithium. Charging time is the energy used divided by the charge efficiency and the charger current, with 10% allowance for the finishing charge.
- DC voltageTaken from the Uniline datasheet for the UPS rating that fits. Enter a different value if you use a different configuration.
- ImportantReal run times depend on the battery maker’s discharge tables. Ask us to confirm the final battery size.
About this calculator
What is the difference between kW and kVA?
kVA is the UPS size; kW is the real power your equipment uses. A load of 6 kW at power factor 0.8 needs 7.5 kVA before margins.
Why does a longer backup need so many batteries?
Batteries deliver less capacity at higher discharge rates, so a short backup at high power needs more rated Ah than the simple energy calculation suggests.
Can I use lithium batteries?
Select lithium (LFP) to see the bank for it. Whether a particular UPS accepts it depends on the model; we confirm with the quotation.