Pick the right cable size from published ratings
Choose the cable type and how it is laid. We use Polycab catalogue current ratings, apply your site derating, check the voltage drop over your length and the short-circuit rating, and show which condition decided the size.
- Size from catalogue ratings
- Derating for your site
- Voltage drop and short-circuit check
Loading the calculator…
Want this checked by an engineer?
Send us your result and we’ll review it and prepare a recommendation and quotation.
Chat on WhatsApp insteadMethod & assumptions
- Current capacityThe table rating for the cable, laying method and size from the Polycab catalogue, multiplied by the derating factors for ground or air temperature, depth, soil resistivity and grouping. The result must be at least the design current.
- Design currentThe load current you enter (or calculated from motor kW or kVA) multiplied by the design margin. For motor feeders the margin is 1.0 unless you set it.
- Voltage drop√3 × I × L × (R cosφ + X sinφ) for three-phase and 2 × I × L × (R cosφ + X sinφ) for single-phase, using catalogue conductor resistance at operating temperature and reactance. If a size has only a published mV/A/m figure, that figure is used.
- Short-circuitThe minimum size is Isc × √t ÷ k with k = 143 (Cu XLPE), 94 (Al XLPE), 115 (Cu PVC), 76 (Al PVC) from IEC 60364-4-43.
- Parallel cablesEach of the parallel cables carries an equal share of the current. Group them with the same length and size.
About this calculator
Which cable type should I choose?
XLPE insulated armoured cable is the usual choice for industrial feeders because of its higher current rating. Copper carries more current for its size; aluminium costs less per ampere in larger sizes.
Why is the cable larger than the current needs?
On long runs the voltage drop limit sets the size, and for high fault levels the short-circuit rating can. The result tells you which condition decided.
What voltage drop should I allow?
Many plants design for about 3% to the motor or feeder end and 5% overall; follow your project specification.
Is this a final design?
No. It is a selection aid. Final sizing depends on the installation drawings, the protective device and the cable maker’s current datasheet.