Know your motor’s current before you select anything

Enter the motor rating, voltage and starting method. We give the full-load current, the starting current for each method and the overload relay setting. Typical IE3 efficiency and power factor are filled in for you; replace them with nameplate values for an exact answer.

You’ll get
  • Full-load current
  • Starting current by method
  • Overload relay setting

Loading the calculator…

Want this checked by an engineer?

Send us your result and we’ll review it and prepare a recommendation and quotation.

How we calculate

Method & assumptions

  • Full-load currentThree-phase: kW × 1000 ÷ (√3 × V × power factor × efficiency). Single-phase: kW × 1000 ÷ (V × power factor × efficiency).
  • EfficiencyIf you leave it at 0 we use the IEC 60034-30-1 IE3 nominal efficiency for a 4-pole motor of that rating. Power factor is a typical catalogue value for that size. A nameplate value always gives a better answer.
  • Starting currentDOL about 6.5× full-load current (typically 5 to 8×; check the motor datasheet). Star-delta draws one third of the DOL current. A soft starter is set to a current limit, 3× by default. A VFD starts at about 1.1×.
  • Overload relayAt the motor full-load current for DOL and soft-starter circuits. For star-delta the relay is in the phase winding, so about 0.58 × full-load current.
  • Horsepower1 HP = 0.746 kW.
FAQ

About this calculator

Why is my nameplate current different from the result?

Efficiency and power factor vary between makes and with the load. Enter the nameplate values under the assumptions to match your motor.

Which starting method should I use?

That depends on the motor size, the load and your supply rules. The starter selection calculator compares DOL, star-delta, soft starter and VFD with tested component sets.

Does this work for 6.6 kV motors?

No. This tool is for low-voltage motors up to 690 V. HV motors need the motor datasheet.

Is the starting current exact?

No. It depends on the motor design. We use a typical multiple and let you change it.