Design a motor feeder: starter, protection and cable
Choose the motor and how it starts: direct on line, star-delta, soft starter or VFD. For DOL and star-delta pick the arrangement: MCCB + contactor + overload relay, MPCB + contactor + overload relay, or MPCB + contactor. You get the ratings and settings of each part and the cable size, not product codes. Add feeders to an MCC list as you go.
- Ratings for every part of the starter
- Tested Type 2 combinations
- MCC list with busbar estimate
Loading the calculator…
Want this checked by an engineer?
Send us your result and we’ll review it and prepare a recommendation and quotation.
Chat on WhatsApp insteadMethod & assumptions
- Starter partsFor DOL and star-delta the protection, contactor and overload relay ratings come from published manufacturer Type 2 coordination charts for 415 V motors, so the parts are a tested combination. Ratings and settings are shown; the make and model are chosen with you in the quotation.
- Three arrangementsMCCB + contactor + overload relay; MPCB + contactor + overload relay; MPCB with built-in overload + contactor. An HRC fuse version is also shown where a chart exists.
- Soft starterRated current at or above the motor current (one step up for heavy starting duty), with a bypass contactor and the short-circuit device the starter maker specifies.
- VFDOnly the drive current rating is given: at or above the motor current for normal duty (pumps, fans) and 1.2 times for heavy duty. Input protection follows the drive maker’s table.
- CableSized from the motor full-load current using Polycab catalogue ratings, derated for 40°C air or 30°C ground, 0.75 m depth and 1.5 K·m/W soil, with the voltage drop you allow.
- MCC totalsConnected load is the sum of the feeders; running current is that total times your diversity. The busbar is the next standard rating above it. The list is kept in your browser only.
About this calculator
What is Type 2 coordination?
After a short circuit the starter can go back into service without replacing parts, apart from contact welds that can be separated easily (IEC 60947-4-1). Type 1 allows damage as long as nobody is at risk.
Why no model numbers?
The tool gives the ratings and settings you need to specify the part. We choose the make and model with you so the combination stays a tested one.
Which starting method should I use?
DOL is the simplest and suits small motors and strong supplies. Star-delta cuts starting current to one third for light starts. Soft starters give adjustable smooth starts. VFDs add speed control.
Do you build the complete panel?
Yes. Use the power system designer to add all your feeders and an incomer, then send the panel for a quotation.