Energy Meters (kWh / kVAh)
Single- and three-phase energy meters for billing and sub-metering of consumption.
On request- StandardIS 13779 / IS 14697, IEC 62053

Download specification sheet (PDF)
Ammeters, voltmeters, frequency meters and other panel indicators.
Every field is optional - tell us what you know and we will confirm the rest in the quotation.
Representative image. The actual product, make and appearance depend on the supplier and your specification.
Also searched as: ammeter, voltmeter, panel meter, digital ammeter and voltmeter, frequency meter, 96 x 96 panel meter
Choose between analogue and digital by what operators need to read. Analogue pointers show trends at a glance and need no auxiliary supply; digital meters give precise values, may show true RMS, and often add alarm relays or communication.
Mistakes include mixing AC and DC scales, ignoring the 1 A or 5 A CT secondary, and leaving no space behind the panel door for terminals. For networked measurement see multifunction meters, and for the supporting CTs see current transformers.
Ratings, dimensions and certification are confirmed against your enquiry. Use Send an enquiry and our engineers will respond within 24 hours.
A moving-iron ammeter uses a pointer driven by the coil current and responds to RMS-like values on AC without auxiliary supply. A digital ammeter measures electronically, shows exact numbers and can offer alarms or outputs. Choose by readability, accuracy and the power available.
The ammeter must be either a 5 A meter with a 400 A scale or a programmable digital meter set to 400/5. A standard 5 A meter with a 0-5 A scale would not display the actual primary current. State the CT ratio when ordering.
A panel meter is a meter mounted on the front of a panel to show a quantity such as current, voltage or frequency. Ammeters, voltmeters and frequency meters are common examples, available in analogue or digital form.
An analogue meter shows the reading with a pointer on a printed scale. A digital meter shows it as numbers on a display. Digital meters are easier to read precisely, while analogue meters are chosen where a pointer view is preferred.
Choose the quantity to be measured, the range and scale, the front size such as 96 x 96 mm, and whether the meter is direct connected or operated through a CT or PT. For CT operated meters, the CT ratio fixes the scale.
Send the quantity to be measured, range, front size, analogue or digital, direct or CT / PT operated with the ratio, auxiliary supply if any and the quantity. SKE Bharat will prepare a quotation from these details.
| Product Type | Panel meter |
|---|---|
| Standard | IS 1248 / IEC 60051 |
| Selection Basis | Quantity measured, range and scale, size (e.g. 96 x 96 mm), direct or CT / PT operated |
| Typical Use | Panel indication |