Analogue & Digital Panel Meters
Ammeters, voltmeters, frequency meters and other panel indicators.
On request- StandardIS 1248 / IEC 60051

Download specification sheet (PDF)
Panel meters that show voltage, current, power, power factor, frequency, energy and harmonics.
Every field is optional - tell us what you know and we will confirm the rest in the quotation.
Representative image. The actual product, make and appearance depend on the supplier and your specification.
Also searched as: MFM, multifunction meter, digital multifunction meter, power analyser, energy analyser, power quality meter
Start with the measurements and the system wiring. A 3-phase 4-wire network needs a meter set for 3P4W, while 3P3W is used for delta systems or Aron connection; entering the wrong mode gives wrong power and power factor readings. Program the CT and PT ratios correctly, and match 1 A or 5 A secondary inputs to the CTs.
A frequent mistake is leaving the voltage taps unfused. Use CTs of sufficient accuracy. Related reading: metering products.
Ratings, dimensions and certification are confirmed against your enquiry. Use Send an enquiry and our engineers will respond within 24 hours.
A multifunction meter displays core electrical values and energy for monitoring. A power analyser adds detail such as individual harmonics, waveform capture, event logs and higher accuracy for audits and power-quality studies. The right choice depends on whether you monitor routinely or diagnose problems.
Typical causes are an incorrect wiring mode (3P3W versus 3P4W), CT phase mismatch, reversed CT polarity or wrong CT and PT ratios entered. Recheck every connection and setting against the manual before blaming the meter itself.
A multifunction meter (MFM) is a digital panel meter that measures several electrical parameters in one unit, such as voltage, current, power, power factor, frequency and energy. Some also show harmonics, and some can send data to other systems.
Both measure many parameters. A power analyser is generally used where detailed power quality data such as harmonics is needed. A basic multifunction meter covers the common readings for panel monitoring. The exact functions depend on the model.
Choose the parameters to be measured, the accuracy class, the CT and PT ratio inputs, whether communication (such as a serial port) is needed, and the panel cut-out size. The auxiliary supply should also be checked.
Send the measurements required, accuracy class, CT / PT ratios, communication needed, panel cut-out size, supply voltage and quantity. Mention the make you prefer. SKE Bharat will prepare a quotation from these details.
| Product Type | Multifunction meter / power analyser |
|---|---|
| Standard | IEC 61557-12, IEC 62053-22 |
| Selection Basis | Measured parameters, accuracy class, CT / PT ratio inputs, communication, panel cut-out size |
| Typical Use | Panel monitoring and power quality |