Potential (Voltage) Transformers
Voltage transformers for metering and protection at medium and high voltage.
On request- StandardIS 3156 / IEC 61869-3

Download specification sheet (PDF)
Current transformers that step down primary current for meters and protection relays.
Every field is optional - tell us what you know and we will confirm the rest in the quotation.
Representative image. The actual product, make and appearance depend on the supplier and your specification.
Also searched as: CT, current transformer, metering CT, protection CT, ring type CT, bar primary CT
A CT is specified by ratio, burden, accuracy class and, for protection, the accuracy limit factor. A 400/5 A CT, for example, should be chosen so that normal load sits at a sensible fraction of the primary rating rather than far below it, where accuracy falls.
Never leave a CT secondary open-circuited while the primary carries current, because a dangerous voltage can develop; short the secondary before disconnecting. Check polarity before commissioning. Pair with a protection relay or a energy meter.
Ratings, dimensions and certification are confirmed against your enquiry. Use Send an enquiry and our engineers will respond within 24 hours.
Pick a primary rating a little above the maximum expected load current, so normal load falls in the upper half of the CT range. Too large a ratio reduces accuracy at low load; too small saturates. The meter or relay input (1 A or 5 A) fixes the secondary.
Generally no. Metering CTs are designed to saturate at modest overcurrent to protect instruments, so a relay may see a distorted signal during a fault and fail to trip correctly. Use a protection-class core with a suitable accuracy limit factor.
A current transformer (CT) reduces a large primary current to a small standard secondary current, usually 1 A or 5 A. It feeds meters and protection relays safely and in proportion to the actual line current.
Choose a primary rating that suits the maximum load current of the circuit, and a secondary of 1 A or 5 A to match the meter or relay. For example, a 400/5 A CT gives 5 A on the secondary when 400 A flows in the primary.
CTs are classified by duty as metering or protection, and by construction as window or ring type, bar primary and wound primary. The type depends on the cable or busbar size, voltage level and the accuracy class needed.
Send the ratio, burden in VA, accuracy class, whether metering or protection, primary voltage, construction type and the cable or busbar size. SKE Bharat will prepare a quotation from these details.
| Product Type | Current transformer |
|---|---|
| Standard | IS 2705 / IEC 61869-2 |
| Selection Basis | Ratio, burden (VA), accuracy class (metering / protection), primary voltage, window / bar / wound type |
| Typical Use | Metering and protection signals |
A practical overview of overcurrent, earth fault and motor protection relays: what each function does, how IDMT curves and grading work, and what to specify when…
7 min readTransformers & Power QualityPlain-language guide to current and potential transformers: ratio, burden, accuracy class for metering and protection, 1 A versus 5 A secondaries, and the mistakes that cause…
7 min read