Array Junction Box
Array Junction Box

Download specification sheet (PDF)

Solar ProductsSKU SKE-SOL-004

Array Junction Box

Reference price
₹2,520 excl. GST
*For reference only, based on market listings for similar products. The actual price is confirmed in our quotation. Please send an RFQ for an exact price.

Weatherproof boxes in the array field that combine PV strings with fuses and surge protection.

On request

Choose your specification

Every field is optional - tell us what you know and we will confirm the rest in the quotation.

WhatsApp

Representative image. The actual product, make and appearance depend on the supplier and your specification.

Overview

Also searched as: AJB, solar array junction box, PV array junction box, DC array junction box, solar string combiner box

Typical applications

  • Ground-mount solar fields
  • Large rooftop arrays
  • Utility plants

Key features

  • Per-string fuses and monitoring options
  • DC surge protection device
  • UV-stabilised outdoor enclosure

Selection notes

An array junction box collects strings at the field, so its ratings must cover the highest DC voltage and current the strings can produce. Use the module's open-circuit voltage at the coldest site temperature, multiplied by the number of modules in a string, and confirm that the box and its components are rated for the system voltage, such as 1000 V or 1500 V DC.

  • String fuses: they must be DC-rated; the module datasheet gives a maximum series fuse rating that sets the upper limit, with the short-circuit current setting the lower.
  • Isolator: a DC switch-disconnector must be rated for DC at the full system voltage.
  • Surge protection: use DC SPDs suitable for PV systems.
  • Enclosure: choose weatherproof protection and UV-resistant material for outdoor mounting, with cable glands sized to the string cables.

Count the strings and leave spare ways. Use the solar calculator for string sizing, and see the DC distribution board and surge protection devices for related equipment.

To quote, please share

  • System size (kWp) and inverter details
  • String / array configuration and DC voltage
  • Number of inputs and outputs
  • Indoor / outdoor mounting and ambient
  • Monitoring and protection requirements

Ratings, dimensions and certification are confirmed against your enquiry. Use Send an enquiry and our engineers will respond within 24 hours.

Frequently asked questions

How do I choose the string fuse rating?

Use the module datasheet: the fuse must be above the normal string current with margin, and not above the module's maximum series fuse rating. It must be a DC-rated fuse suitable for the system voltage. Confirm with your designer.

Why does open-circuit voltage at low temperature matter?

PV module voltage rises as temperature falls. In cold conditions, the string voltage can exceed its rating if the string is long. The box and inverter must withstand that maximum voltage. Verify it at the lowest recorded site temperature, using the module temperature coefficient.

Can AC components be used in a DC junction box?

No. DC arcs do not extinguish as easily as AC arcs, so isolators, fuses and breakers must be specifically rated for DC at the full voltage. AC-only parts in DC service are a fire risk, so the box, fuses and isolators must all carry a DC rating.

What is an array junction box used for?

An array junction box combines the outputs of several PV strings in the solar field into fewer outgoing cables. It usually holds string fuses and surge protection and is weatherproof so it can be mounted outdoors near the modules.

What is the full form of AJB in solar?

AJB stands for Array Junction Box. It sits in the array field between the PV strings and the inverter or DC distribution board, collecting the string cables and protecting them before the power travels to the inverter.

What is the difference between a junction box and a distribution box?

A junction box is mainly for joining and branching cables, while a distribution board houses protective devices that feed several circuits. A solar array junction box does both in a small way, as it combines strings and holds fuses and surge protection.

What details are needed for an array junction box quotation?

Send the number of strings, string current, system voltage (1000 V or 1500 V DC), fuse and surge protection requirements, enclosure material and any monitoring needs. SKE Bharat prepares the quotation within 24 hours.

Technical specification

Product TypeArray junction box (AJB)
StandardIEC 61439, IEC 60364-7-712
Voltage ClassDC, up to 1000 / 1500 V
ConstructionPolycarbonate or sheet-steel
Protection DegreeIP65
Typical UseString combining in the field