Choose the SPD type by where it sits in the installation. Type 1 handles direct lightning currents at the incoming point of buildings with external lightning protection; Type 2 sits at distribution boards; Type 3 gives local protection at sensitive equipment. In many installations they work as a coordinated cascade.
Keep connection leads as short and straight as possible, because long leads add voltage and reduce protection. Connect to a low-resistance earth; see earthing materials. A poor earth makes the SPD ineffective. For solar arrays pair with an array junction box.
Ratings, dimensions and certification are confirmed against your enquiry. Use Send an enquiry and our engineers will respond within 24 hours.
They differ in the surge they are designed to handle and their position. Type 1 takes partial lightning currents at the service entrance, Type 2 handles switching and induced surges at distribution boards, and Type 3 provides fine protection at the equipment.
A surge current flowing through a long lead creates a voltage drop that adds to the SPD's protection level, so the equipment sees a higher voltage than expected. Short, direct connections to the busbar and earth maintain the intended protection.
SPD stands for Surge Protective Device (also called surge protection device). It limits transient overvoltages from lightning and switching by diverting the surge current to earth, which protects panels, drives, electronics and other connected equipment.
Type 1 SPDs handle lightning currents and are used at the service entrance. Type 2 SPDs are fitted in distribution boards and panels. Type 3 SPDs protect sensitive equipment close to the load. DC SPDs are used for solar arrays.
An MCB protects against overload and short-circuit current. An SPD protects against short-duration voltage surges. They do different jobs, and an SPD is normally installed with a suitable fuse or breaker as backup protection, as the SPD maker advises.
Choose the type (1, 2 or 3), AC or DC for solar, the system voltage and earthing arrangement, number of poles for single or three phase, and the discharge current rating. Send these details to SKE Bharat for a quotation within 24 hours.
| Product Type | Surge protective device |
|---|---|
| Standard | IEC 61643-11 (AC), IEC 61643-31 (DC) |
| Selection Basis | Type (1 / 2 / 3), system voltage, discharge current, AC or DC (solar) |
| Typical Use | Surge protection at panels and solar arrays |