Manual and motorised changeover switches for transfer between two supplies, such as mains and generator.
Every field is optional - tell us what you know and we will confirm the rest in the quotation.
Representative image. The actual product, make and appearance depend on the supplier and your specification.
Also searched as: COS switch, mains generator changeover switch, manual changeover switch, automatic changeover switch, on load changeover switch, transfer switch
The two critical choices are the number of poles and the switch rating. Use a four-pole switch if the neutral must be switched between mains and generator, which avoids neutral paralleling; many installations use three-pole switching with a solid neutral, so follow the earthing scheme and confirm with an engineer. The current rating should cover the full load, with the utilisation category suited to the load, since inductive loads need more than resistive ones.
Check generator size and starting current before selecting. Mistakes include undersized switches on generator loads and forgetting the transfer delay setting. Panels are available as auto change over panels and AMF panels.
Ratings, dimensions and certification are confirmed against your enquiry. Use Send an enquiry and our engineers will respond within 24 hours.
It depends on the earthing and neutral arrangement. Four-pole switching also transfers the neutral and is common where the generator neutral is separately earthed. Three-pole with a solid neutral is used in other systems. Confirm the scheme with your electrical engineer.
A manual changeover is operated by hand when power fails. An automatic or motorised changeover, with an ATS controller, senses mains failure, starts the generator and transfers the load without operator action, usually with set time delays.
A changeover switch transfers a load between two supplies, most commonly mains and a generator, so that only one supply feeds the load at a time. It prevents the two sources from being connected together.
They are broadly manual and motorised. A manual switch is operated by hand, while a motorised or automatic changeover uses a motor drive and a controller to transfer on supply failure. Poles and neutral arrangement vary by application.
A changeover switch selects between two supplies. A bypass switch is used with equipment such as a UPS or automatic transfer scheme so the load can be fed directly while the equipment is isolated for maintenance.
Select by load current, number of poles, with or without neutral switching, and manual or motorised operation. Send these details with quantity and make preference. Quotations are prepared from the details you send, so share your requirement and SKE Bharat will respond within 24 hours.
| Product Type | Changeover switch |
|---|---|
| Standard | IEC 60947-3, IEC 60947-6-1 |
| Selection Basis | Current rating, poles, manual or motorised, with or without neutral |
| Typical Use | Mains to generator transfer |