Current Transformers (CT)
Current transformers that step down primary current for meters and protection relays.
On request- StandardIS 2705 / IEC 61869-2

Download specification sheet (PDF)
Numerical and electromechanical protection relays for feeders, motors, generators and transformers.
Every field is optional - tell us what you know and we will confirm the rest in the quotation.
Representative image. The actual product, make and appearance depend on the supplier and your specification.
Also searched as: overcurrent relay, OC EF relay, overcurrent and earth fault relay, IDMT relay, numerical protection relay, feeder protection relay
List the functions you need before comparing makes. A feeder usually needs phase overcurrent (50/51) and earth fault (50N/51N); a motor adds thermal overload (49), locked-rotor, unbalance or negative-sequence and under-current; a transformer may add differential (87T). Numerical relays combine these in one unit, while simple electromechanical or analogue types do one job each.
Settings must come from a protection coordination study, not a copy of the previous job, and should be checked by a qualified engineer. Typical faults: reversed CT polarity and wrong earth-fault CT arrangement. See current transformers and VCB breakers for the related primary equipment.
Ratings, dimensions and certification are confirmed against your enquiry. Use Send an enquiry and our engineers will respond within 24 hours.
Functions 50 and 51 respond to phase overcurrent, instantaneous and time-delayed respectively. 50N and 51N do the same for earth fault current, using a residual or core-balance CT arrangement. Most feeders use both so phase and earth faults are cleared at different sensitivities.
A numerical motor protection relay generally covers overload, short-circuit, unbalance and earth fault for that motor circuit. It is not a substitute for protection of the upstream bus or transformer. Share the motor rating, voltage and starting method when requesting a suitable relay.
An overcurrent relay monitors current, usually through a current transformer, and sends a trip signal when current exceeds a set value for a set time. The circuit breaker is the switching device that then opens and interrupts the current.
IDMT stands for Inverse Definite Minimum Time. The relay operates faster as the fault current increases, with a definite minimum operating time at very high currents. This helps protection settings coordinate between feeders.
An overload relay, thermal or electronic, is fitted with a contactor to protect a motor from sustained overload. An overcurrent relay is used on feeders and larger equipment with settable current and time, and it trips a circuit breaker.
Send the protection functions needed, such as overcurrent and earth fault, CT secondary of 1 A or 5 A, auxiliary supply voltage, panel cut-out, communication requirement and number of relays. SKE Bharat sends a quotation within 24 hours.
| Product Type | Protection relay |
|---|---|
| Standard | IEC 60255 |
| Selection Basis | Protection functions needed, CT / PT inputs, auxiliary supply, communication, panel cut-out, I/O |
| Typical Use | Protection of MV and LT feeders and motors |
A practical overview of overcurrent, earth fault and motor protection relays: what each function does, how IDMT curves and grading work, and what to specify when…