Oil-filled distribution transformers that step grid voltage down to the utilisation level for plants, campuses and utilities.

On request

Describe what you need

Made to order against your specification. Fill what you know; our engineers will confirm the rest.

WhatsApp

Representative image. The actual product, make and appearance depend on the supplier and your specification.

Overview

Also searched as: oil filled distribution transformer, 11 kV distribution transformer, step down transformer, ONAN distribution transformer, DT transformer

Typical applications

  • Factory and plant incoming supply
  • Commercial and residential complexes
  • Utility distribution networks

Key features

  • Sealed or conservator construction
  • Star-rated efficiency options
  • Fittings and tests per standard

Selection notes

Distribution transformers are usually bought on a standard specification, so small details decide long-term cost. Start with kVA, primary and secondary voltage, vector group (Dyn11 is common in India), tap range and the standard, such as IS 1180 for ratings it covers.

  • Losses and star rating: a higher energy efficiency level costs more up front but reduces no-load and load loss over the years; compare using the loading you expect.
  • Sealed or conservator: sealed units need less upkeep, while conservator types are common in bigger ratings; see oil immersed transformers.
  • Sizing: use the transformer sizing calculator to check against load and future growth.

Typical mistakes are oversizing, which raises no-load loss and lowers efficiency at light load, and omitting a plan for the LV side, where a bus duct or cable arrangement must handle high current. Verify the earthing, fittings and tests required by your DISCOM. Standard ratings and approvals should be confirmed with the manufacturer.

To quote, please share

  • kVA / MVA rating and phases
  • Primary / secondary voltage and frequency
  • Vector group, impedance and tap range
  • Cooling and installation (indoor / outdoor, altitude, ambient)
  • Applicable standard and test requirements

Ratings, dimensions and certification are confirmed against your enquiry. Use Send an enquiry and our engineers will respond within 24 hours.

Frequently asked questions

What does vector group Dyn11 mean?

D is a delta-connected primary, yn a star secondary with an accessible neutral, and 11 the clock position, meaning the LV leads the HV by 30 degrees. It is widely used in distribution because it handles unbalanced single-phase loads well. Always match the vector group for parallel operation.

How do I choose the right kVA for a plant transformer?

Add up maximum demand, apply diversity, allow room for growth, and avoid running it far below capacity. Overloading shortens life, but heavy oversizing wastes energy. Use the transformer sizing calculator as a starting point and verify the load profile.

What is a distribution transformer?

A distribution transformer is the last voltage step before the supply reaches the user. It steps the grid voltage, such as 11 kV or 22 kV, down to the utilisation voltage of about 433 V used by plants, campuses and consumers.

What is the difference between a power transformer and a distribution transformer?

Power transformers work at higher voltages in substations and generating stations and usually run near full load. Distribution transformers work at the load end at lower voltage and are loaded variably through the day, so they are designed for good all-day efficiency.

Which standard applies to distribution transformers in India?

Distribution transformers are commonly built to IS 1180, with IS 2026 as the general power transformer standard. The standard and efficiency level that apply to your order depend on your utility or project specification.

What details are needed to quote a distribution transformer?

Send the kVA rating, primary and secondary voltage, vector group, cooling type, tap changer requirement, impedance, indoor or outdoor use and any loss level requirement. Quotations are prepared within 24 hours of receiving the details.

Technical specification

Transformer TypeOil immersed, distribution
CoolingONAN
StandardIS 1180 / IS 2026
Voltage Class11 kV or 22 kV / 433 V
Vector GroupDyn11 (typical)
Tap ChangingOff-circuit tap switch